For somewhat more money ~ $30 and up there are multimeters with a
built-in thermocouple measuring circuit, and which do the ice-water
reference electronically. Typically they use type K (chromel alumel)
thermocouples. That wire is also available from McMaster.
Equalizing the Temperature
For control I put one thermocouple right in the middle of the length of
the tube held in place with a hose clamp, and several more at 6"
intervals out to the end for test purposes in getting the temperature
equal. I later realized I didn't need the others because I
could bore a small hole in an end cap and insert a thermocouple long
enough to reach the middle and move it a measured amount to get the
temparature at other locations. Before I started testing, I put one
wrap of fiberglass information over the length of the tube between the
two bricks.
One Wrap of Fiberglass.
The stuff I used was about 3" wide by about 1/4" thick. Then
I started to test. I ran the dimmer control up to full power until
around 175° C or 350° F was reached and then backed off until I found a
setting where that temperatue would hold. After it had come to
equilibrium, I measured the other positions. Here are the results.
| Middle |
6" |
12" |
18" |
24" |
30" |
| 172° |
172° |
160° |
150° |
138° |
96° |
This was not too bad but I needed to do better. The results suggested
more insulation on the ends. A second layer between 30" and 16" from
the middle gave the following results
| Middle |
6" |
12" |
18" |
24" |
30" |
| 170° |
170° |
168° |
168° |
162° |
116° |
Considerable improvement, seemed to be on the right track. Added a
third layer between 30" and 20" from the middle for these results.
| Middle |
6" |
12" |
18" |
24" |
30" |
| 172° |
174° |
174° |
175° |
174° |
128° |
This is looking about right. Applied the same wraps to the other end
for these results.
| Middle |
6" |
12" |
18" |
24" |
30" |
| 170° |
174° |
179° |
181° |
181° |
140° |
Second and Third Wraps
Applied.
Rather than keep chasing this, I measured with the thermocouple on the
inside to get this result
| Middle |
6" |
12" |
18" |
24" |
30" |
| 177° |
177° |
177° |
179° |
177° |
138° |
So for 24" on either side of the middle it looks like I have a
reasonably uniform temperature. The heating cord only runs to
the 30" point so there is 6" unheated on the ends which accounts for
the drop there. It does help to add a little wrap of fiberglass on the
end as shown here.
Wrap on the End
To improve on this, it seemed to need more heat near the ends, so the
cord wraps were redistributed as shown below.
Redistributed Heating Cord--Same on Right End
With the insulation reinstalled as before the result of this was
| Middle |
6" |
12" |
18" |
24" |
27" |
30" |
| 172° |
172° |
170° |
172° |
180° |
185° |
172° |
The temperature drop at the end was moved further out and
compressed over a smaller region, but more tweaking of the insulation
was needed. As I did this the temperature at the middle would drift
around even is extra insulation was nowhere near the middle, so at this
point I decided to put a PID controller on with a
thermocouple attached to the middle for a control point. This
stabilized the temperature at the middle quite nicely and made the
further adjustment of the insulation to equaliize the temperature much
easier. My final result was
| Middle |
6" |
12" |
18" |
24" |
27" |
30" |
| 178° |
178° |
178° |
174° |
176° |
179° |
172° |
Wiring Details
The heating cord is a single conductor with a lead coming out each end. Wiring
it, and connecting it to power is as shown in the next two pictures.
Wiring to 3 Condutor
Power Cord
A cheap source of a good 3 conductor cord was a $3 strip outlet which I
scrapped for it. The black wire is connected to one end of heating
cord, the white wire to the other end, and the green wire, which is
ground, is connected to the copper tube. Black, white and green are
standard electrical code colors to the hot side, the neutral side, and
ground respectively. Connections are made with wire nuts. The wires are
held in place with insulated staples.
Connection at the Other
End
The PID Controller
The following is a very explicit description of how I put in a specific
PID controller.
The PID Controller Parts
The PID controller I got was from Auber Intruments, their
Universal
1/32 DIN PID Temperature Controller. To go with it I got a 25
amp
solid
state relay. I built it up in a 3x4x5" electronic project box
which I go from a local electronics store. Other parts needed were from
the local hardware store.
They were
- A three conductor extension cord about 6' long.
- NM (non-metallic) connectors for holding the cord where it
passes in and out of the box, 2 needed.
- Spade lugs for #16-#14 wire to fit #6 stud for connecting
to the controller.
- Spade lugs for #16-#14 wire to fit #10 stud for
connecting to the power terminals of the relay and to ground.
- 10-32 1/2" screws and nuts to hold the relay to
the box--2 needed
- Black, white, and green stranded copper wire, #16 or #14,
about 2' of each.
- Toggle switch single pole single throw (SPST) with screw
terminals.
Assembly
Cut a rectangular hole in the box about 0.900" x 1.800" for the control
unit. Put it where it won't crowd the relay which is screwed to the
box. Bore holes for the relay mounting, the toggle switch and the NM
connectors.
The box with all the
holes cut
Mount all the parts as shown in the picture below. There are spring
clips built into the control unit which hold it when it is slid into
the hole.
Cut the extension cord about 14" from the socket end and
strip about 4" of the outer cover off each of the cut ends and
pass them through the NM connectors and clamp them with the screws.
Assembled Box
Wiring the Contoller
To make connection to a spade lug, strip off about !/4" of insulation
from a wire, insert it in the lug and crimp it with an electricians tool
Electrician's Tool
Starting the Wiring
- Crimp a #10 spade lug to the black wire of the output cord
and connect to the T1 terminal on the relay. There is gray
plastic cover on the relay you will have to take off to get at the
terminals.
- Crimp a #10 spade lug to the green wire of the output cord
and ground it by connecting to one of the mounting
screws of the relay.
More Wiring
- Crimp a #10 spade lug to the green wire of the input cord
and ground it by connecting to the other mounting screw of the relay.
- Crimp a #6 spade lug to the black wire of the input cord
and connect it to a termiinal of the toggle switch.
- Take a 4" piece of black wire, crimp a #6 lug to one end and
connect to the other teminal of the switch. To the other end of the
wire, crimp a #10 lug and connect to L1 terminal of
the relay.
- With another 4" piece of black wire, crimp #6 lugs to both
ends and connect between the same terminal of the switch as the last
one and the terminal 1 of the controller.
- Crimp a #6 lug to one end of a 4" piece of white wire and
connect to the terminal 2 of he controller. Strip the other end and
twist together with the white wires from the input and output cords and
screw a wire nut on the twist.
- Crimp a #6 lug on one end of a 4" piece of green wire and
connect to termal 3 of the controller. Crimp a #10 lug to the other end
and ground it by connecting it to one of
the mounting screws of the relay.
- Crimp #6 lugs to both ends of a 4" piece of black wire.
Connect one end to terminal 9 of the controlller and the
other to the A2(-) terminal of the relay..
- Crimp #6 lugs to both ends of a 4" piece of white wire.
Connect one end to terminal 10 of the controller and the other to the
A1(+) terminal of the relay.
- Make a thermocouple as described above.
Connect the copper wire (blue insulation) to terminal 7 of the
controller and the constantan wire (red insulation) to
teminal 6.
- Clamp the junction end of the thermocouple to the copper
tube of the oven about in the middle with a stainless steel hose clamp.
Setup and Operation
The controller comes with a manual
which may be confusing. Hopefully this procedure list will help.
To
setup the controller plug it in, but don't plug in the oven. I strongly
recommend running it from a GFI (Ground Fault Interrupt) protected
outlet. Turn it
on. On the front panel are four buttons,
Set,
>,
^, and
v. The display has four columns.
To Setup:
- Push the Set button
- Enter the code for setup, 0089. Do this by using the > button choose the column and the ^ and v buttons to set the numbers.
- Push the Set button. IntY should appear in the display. Push Set again. A t should appear in the display indicating that a copper constantan type T thermocouple is to be used, If t does not appear push the ^ button until it does. Push Set.
- Push ^, outY should appear. Push Set, if 2 does not appear, push ^ until it does. Push Set.
- Push ^, Hy should appear. Push Set, if 0003 does not appear, use the >, ^ and <
span style="font-weight: bold;">v buttons to change it to 0003. Push Set.
- Push ^. Atdu should appear, Push Set. If 000 does not appear, use the >, ^ and v buttons to change it to 000. Push Set.
- Push ^. PSb should appear. Push Set. if 0000 does not appear, use the >, ^ and v buttons to change it to 0000. Push Set.
- Push ^. rd should appear. Push Set. if 0 does not appear, use ^ to change it. Push Set.
- Push ^. Corf should appear. Push Set. Use ^ to set it to 1 to display temperature in °F or 0 for °C. Push Set.
- End should appear. Setup is done.
Note that if you take too long set a parameter, the controller will revert to normal operation and you will have
to re-enter
0089 and use ^ until you get to the last parameter you were going to set.
To Set a Temperature:
- Push the Set button.
- Enter the code for temperature setting, 0001. Do this by using the > button choose the column and the ^ and v buttons to set the numbers.
- Push the Set button. Su should appear in the display. Push Set again. Use the >, ^ and v buttons to change it to the desired value. Push Set.
- Push ^. AH1 should appear. Push Set. Use the >, ^ and v buttons to set the high temperature where the alarm (AL) light goes on. Push Set.
- Push ^. AL1 should appear. Push Set. Use the >, ^ and v buttons to set the temperature where the alarm (AL) light goes off. Push Set.
- Push ^. End should appear. Push Set.
Now turn off the controll
er, connect the oven, and turn it on again. At this point if you press and hold the
>
until the AT light flashes, the device will autotune its PID
parameters. The indicated temperature will rise a few degrees above the
set point, the drop a few below and finally stabilize as this process
goes on. The AT light stops flashing when it is done. This may
take awhile, perhaps 15 minutes.
At this point it's done.